10.2 (Optional) Connecting Generator Start/Stop
Cables (ATS Input)
Prerequisites
Pre-fab. modules and external cable trays have been installed.
Procedure
Step 1 Connect the generator start/stop cables to the terminals on the XT2 terminal
block.
Table 10-1 Generator start/stop cable connection
Cable Connecting Position in the Device
Generator start/stop
Issue 07 (2022-12-15)
NO TE
Here connecting one of the cables is used as an example. XT2-6 is a normally open contact,
XT2-7 is a common contact, and XT2-8 is a normally closed contact.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Installing Cables Outside Pre-fab. Modules
Generator Start
Generator Com
Generator Stop
Cable Connecting
Position in the UPS
XT2-6
XT2-7
XT2-8
100