This section describes only how to install water refill pipes on water refill and
drainage ports of the FusionModule1000. Other water refill pipes are routed and
installed depending on onsite situations under the guidance of onsite supervisors.
Prerequisites
●
●
Context
Refill water to humidifiers in real time when the cooling system is operating to
ensure normal system operation.
When the system is operating, ensure that the automatic water refill valve has the
water source available with the water pressure of 0.1 MPa to 0.7 MPa.
Preparations
Tools: hacksaw, protective gloves, hot melt device
Materials: DN25 PP-R pipe (with an outer diameter of 25 mm, to be purchased
onsite), bend, straight connector, 10 mm thick thermal insulation foam
Skill requirement: skilled technician
Procedure
Step 1 Open the rear door of the pre-fab. module.
Issue 07 (2022-12-15)
Installing External Pipes for Smart
Drainpipes and auxiliary refill devices that meet requirements have been
prepared.
The positions for installing water refill pipes and drainpipes have been
specified.