3.5 Water Refill and Drainage Requirements

3.5.1 Water Refill Requirements

Table 3-1 Water refill requirements
Port Position
Port
Dimensions
For the
DN25 PP-R
humidifier in
pipe port
the smart
cooling
product
Issue 07 (2022-12-15)
A pre-fab. module can be grounded using ground lugs or ground cables.
Ground lug method: Use a ground lug made of hot-dip zinc-coated flat
steel sheet with a cross-sectional area of 40 mm x 4 mm, connect one
end of the ground lug to the pre-buried ground grid, and connect the
other end to the pre-fab. module ground point. When a ground grid is
pre-buried, the ground lug must be long enough to connect to a ground
point on the pre-fab. module.
Ground cable method: Use a 95 mm
one end of the cable to the pre-buried ground grid, and connect the
other end to the pre-fab. module ground point. When a ground cable is
used, the ground cable must be routed through a plastic-coated metal
hose.
NO TE
● The screw reserved at a ground point is an M12 screw.
● A pre-fab. module can be grounded in the TN-S or TN-C-S mode.
The water refill ports for humidifiers must supply water continuously when
the FusionModule1000 is operating.
Table 3-1
describes the requirements on the water refill ports and pipes.
Water
Pressure
Requirement
0.1–0.7 MPa
Table 3-2
describes the water quality requirements.
Table 3-2 Water quality requirements
Item
Hydrogen ion
Conductivity at 20°C (σ
Inlet water hardness specifications
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
cable as the ground cable, connect
Transient
Water Flow
≥ 1.2 L/min
Allowed Value
pH: 7–8.5
300–1250 μS/cm
a
)
20
≤ 100 mg/L
b
3 Site Requirements
Pipe Pressure
Remarks
Bearing
Capacity
1 MPa
Consider
connectivity
to water refill
devices.
28