Parameter Descriptions

3.7 H-## High Perf Parameters

Parameter group related to high performance functions in
the drive.
3.7.1 H-0# High Perf Operations
3
3
Parameters to restore factory setting, configure auto reset,
fan operation, reverse lock and start mode (catch a
spinning load).
H-01 Option Detection
Selects the behavior of the frequency converter when a change
in the option configuration is detected.
Option:
[0]
Protect Option
*
Config.
[1]
Enable Option
Change
H-03 Restore Factory Settings
Option:
[0]
Normal
operation
*
[2]
Restore
Factory
Settings
64
Function:
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
Changes frequency converter settings
and is used when modifying the
system configuration. This parameter
setting returns to [0] Protect Option
Config. after an option change.
Function:
Use this parameter to specify normal operation,
to perform tests, or to restore all parameters
except:
Parameter ID-03 Power Up's.
Parameter ID-04 Over Temp's.
Parameter ID-05 Over Volt's.
This function is active only when the power is
cycled (power off/power on) to the frequency
converter.
Normal operation of the frequency converter
with the motor in the selected application.
[2] Restore Factory Settings Resets all parameter
values to default settings, except for:
Parameter ID-03 Power Up's.
Parameter ID-04 Over Temp's.
Parameter ID-05 Over Volt's.
The frequency converter resets during the next
power-up.
Parameter H-03 Restore Factory Settings also
reverts to the default setting [0] Normal
operation.
H-04 Auto-Reset (Times)
Option:
[0]
Manual reset
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10]
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite auto reset
*
NOTICE
The motor may start without warning. If the specified
number of AUTOMATIC RESETs is reached within 10
minutes, the frequency converter enters Manual reset [0]
mode. After the Manual reset is performed, the setting
of parameter H-04 Auto-Reset (Times) reverts to the
original selection. If the number of automatic resets is
not reached within 10 minutes, or when a Manual reset
is performed, the internal AUTOMATIC RESET counter
returns to zero.
H-05 Auto-Reset (Reset Interval)
Range:
10 s
[0 - 600
*
s]
02/2016 All rights reserved.
Function:
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
Select [0] Manual reset, to perform a
reset via [RESET] or via the digital
inputs.
Select Automatic reset x 1...x20 [1]-
[12] to perform between one and
twenty automatic resets after
tripping.
Select [13] Infinite Automatic Reset
for continuous resetting after
tripping.
Function:
Enter the time interval from trip to start of the
automatic reset function. This parameter is
active when parameter H-04 Auto-Reset (Times)
is set to [1]–[13] Automatic reset.