2.1.2 Quick Transfer of Parameter Settings
between Multiple Frequency
Converters
Once the set-up of a frequency converter is complete,
store the data in the keypad or on a PC via Drive Control
Tool Software DCT 10.
Illustration 2.9 Keypad
Data storage in keypad
NOTICE
Stop the motor before performing this operation.
To store the data in the LCP:
1.
Go to parameter K-50 Keypad Copy.
2.
Press the [OK] key.
3.
Select [1] All to keypad.
4.
Press the [OK] key.
All parameter settings are now stored in the keypad
indicated by the progress bar. When 100% is reached,
press [OK].
Connect the keypad to another frequency converter and
copy the parameter settings to this frequency converter as
well.
Data transfer from keypad to frequency converter
DET-618D
AF-650 GP™ Programming Guide
NOTICE
Stop the motor before performing this operation.
To transfer the data from the LCP to the frequency
converter:
1.
2.
3.
4.
The parameter settings stored in the keypad are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].

2.1.3 Display Mode

In normal operation, up to 5 different operating variables
can be indicated continuously in the middle section: 1.1,
1.2, and 1.3, as well as 2 and 3.

2.1.4 Display Mode - Selection of Readouts

It is possible to toggle between 3 status readout screens
by pressing [Status].
Operating variables with different formatting are shown in
each status view further in this section.
Table 2.1 shows the measurements that can be linked to
each of the operating variables. When options are
mounted, additional measurements are available.
Define the links via
Each readout parameter selected in parameter K-20 Display
Line 1.1 Small to parameter K-24 Display Line 3 Large has its
own scale and digits after a possible decimal point. The
larger the numeric value of a parameter is, the fewer digits
are displayed after the decimal point.
Example: Current readout 5.25 A, 15.2 A, 105 A.
Operating variable
Parameter DR-00 Control Word
Parameter DR-01 Reference [Unit]
Parameter DR-02 Reference [%]
Parameter DR-03 Status Word
Parameter DR-05 Main Actual Value [%]
Parameter DR-10 Power [kW]
Parameter DR-11 Power [hp]
Parameter DR-12 Motor Voltage
02/2016 All rights reserved.
Go to parameter K-50 Keypad Copy.
Press the [OK] key.
Select [2] All from keypad.
Press the [OK] key.
Parameter K-20 Display Line 1.1 Small.
Parameter K-21 Display Line 1.2 Small.
Parameter K-22 Display Line 1.3 Small.
Parameter K-23 Display Line 2 Large.
Parameter K-24 Display Line 3 Large.
2
Unit
hex
[Unit]
%
hex
%
[kW]
[hp]
[V]
15
2