GE AF-650 GP Programming Manual page 51

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
[64]
Comparator 4
[65]
Comparator 5
3
3
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
Logic
Controller
Digital Output
A
[81]
Logic
Controller
Digital Output
B
[82]
Logic
Controller
Digital Output
C
[83]
Logic
Controller
Digital Output
D
[84]
Logic
Controller
Digital Output
E
[85]
Logic
Controller
50
See parameter group LC-1#. If Comparator
4 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-1#. If Comparator
5 is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 0
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 1
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 2
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 3
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 4
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter group LC-4#. If Logic Rule 5
is evaluated as TRUE, the output will go
high. Otherwise, it will be low.
See parameter LC-52 Logic Controller Action.
The output will go high whenever the
Logic Controller Action [38] Set dig. out. A
high is executed. The output will go low
whenever the Logic Controller Action [32]
Set dig. out. A low is executed.
See parameter LC-52 Logic Controller Action.
The input will go high whenever the Logic
Controller Action [39] Set dig. out. A high is
executed. The input will go low whenever
the Logic Controller Action [33] Set dig. out.
A low is executed.
See parameter LC-52 Logic Controller Action.
The input will go high whenever the Logic
Controller Action [40] Set dig. out. A high is
executed. The input will go low whenever
the Logic Controller Action [34] Set dig. out.
A low is executed.
See parameter LC-52 Logic Controller Action.
The input will go high whenever the Logic
Controller Action [41] Set dig. out. A high is
executed. The input will go low whenever
the Logic Controller Action [35] Set dig. out.
A low is executed.
See parameter LC-52 Logic Controller Action.
The input will go high whenever the Logic
Controller Action [42] Set dig. out. A high is
executed. The input will go low whenever
the Logic Controller Action [36] Set dig. out.
A low is executed.
See parameter LC-52 Logic Controller Action.
The input will go high whenever the Logic
Controller Action [43] Set dig. out. A high is
02/2016 All rights reserved.
Digital Output
executed. The input will go low whenever
F
the Logic Controller Action [37] Set dig. out.
A low is executed.
[120] Local
Output is high when
reference
parameter F-02 Operation Method = [2]
active
Local or when parameter F-02 Operation
Method = [0] Linked to hand auto at the
same time as the keypad is in Hand mode.
[121] Remote
Output is high when
reference
parameter F-02 Operation Method = [1]
active
Remote or [0] Linked to hand/auto while the
keypad is in [Auto] mode.
[122] No alarm
Output is high when no alarm is present.
[123] Start
Output is high when there is an active
command
Start command (i.e. via digital input bus
active
connection or [Hand] or [Auto]), and no
Stop or Start command is active.
[124] Running
Output is high when the frequency
reverse
converter is running counter clockwise (the
logical product of the status bits 'running'
AND 'reverse').
[125] Drive in hand
Output is high when the frequency
mode
converter is in [Hand mode] (as indicated
by the LED light above [Hand]).
[126] Drive in auto
Output is high when the frequency
mode
converter is in [Hand] mode (as indicated
by the LED light above [Auto]).
E-20 Terminal 27 Digital Output
Choices are described under E-2#
E-21 Terminal 29 Digital Output
Choices are described under E-2#
E-24 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 [4], Relay
6 [5], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Choices are described under E-2#
E-26 On Delay, Relay
Array [20]
Range:
Function:
0.01 s
[0.01 -
Enter the delay of the relay cut in time.
*
600 s]
Select 1 of 2 internal mechanical relays in an
array function. See parameter E-24 Function
Relay for details.