Parameter Descriptions

3.18 DR-## Data Read-outs

Parameter group related to data readouts in the drive for
references, voltages, control, alarms, warnings, and status
words.
3
3
3.18.1 DR-0# General Status
Parameters to view the calculated references, the active
control word, and status word.
DR-00 Control Word
Range:
0
[0 - 65535] View the control word sent from the frequency
*
DR-01 Reference [Unit]
Range:
0 ReferenceFeed-
backUnit
*
DR-02 Reference [%]
Range:
0 %
[-200 -
*
200 %]
DR-03 Status Word
Range:
0
[0 - 65535] View the status word sent from the frequency
*
DR-05 Main Actual Value [%]
Range:
0 %
[-100 - 100 %] View the 2-byte word sent with the status
*
DR-09 Custom Readout
Range:
0 CustomRea-
doutUnit
*
128
Function:
converter via the serial communication port in
hex code.
Function:
[-999999 -
View the present reference
999999
value applied on impulse or
ReferenceFeed-
analog basis in the unit
backUnit]
resulting from the configu-
ration selected in
parameter H-40 Configu-
ration Mode (Hz, Nm, or
RPM).
Function:
View the total reference. The total reference
is the sum of digital, analog, preset, bus,
and freeze references, plus catch up and
slow down.
Function:
converter via the serial communication port in
hex code.
Function:
word to the fieldbus master reporting the
main actual value.
Function:
[0 - 0 Custom-
View the value of custom
ReadoutUnit]
readout from
parameter K-30 Unit for Custom
Readout to
parameter K-32 Max Value of
Custom Readout
3.18.2 DR-1# Motor Status
Parameters to view the motor status values.
DR-10 Power [kW]
Range:
0 kW
[0 -
*
10000
kW]
DR-11 Power [hp]
Range:
0 hp
[0 -
*
10000 hp]
DR-12 Motor Voltage
Range:
0 V
[0 - 6000 V] View the motor voltage, a calculated value
*
DR-13 Frequency
Range:
0 Hz
[0 - 6500 Hz] View the motor frequency, without
*
DR-14 Motor current
Range:
0 A
[0 - 10000
*
A]
DR-15 Frequency [%]
Range:
0 %
[-100 -
*
100 %]
02/2016 All rights reserved.
Function:
Shows motor power in kW. The value shown is
calculated based on the actual motor voltage
and motor current. The value is filtered, and
therefore approximately 1.3 s may pass from
when an input value changes to when the
data readout values change. The resolution of
readout value on fieldbus is in 10 W steps.
Function:
View the motor power in hp. The value
shown is calculated based on the actual
motor voltage and motor current. The value is
filtered, and therefore approximately 1.3 ms
may pass from when an input value changes
to when the data readout values change.
Function:
used for controlling the motor.
Function:
resonance damping.
Function:
View the motor current measured as an
average value, I
. The value is filtered, and
RMS
thus approximately 1.3 s may pass from when
an input value changes to when the data
readout values change.
Function:
View a 2 byte word reporting the actual motor
frequency (without resonance damping) as a
percentage (scale 0000–4000 hex) of
parameter F-03 Max Output Frequency 1. Set
parameter PB-16 PCD Read Configuration index 1
to send it with the status word instead of the
MAV.