Parameter Descriptions
3.7.7 H-7# Adjustable Warnings
Parameters to configure the warnings limits for current,
speed, reference, and feedback.
Warnings are shown on the keypad and can be
programmed to be outputs or to be readout via fieldbus in
the extended status word.
Illustration 3.32 Adjustable Warnings
H-70 Warning Current Low
Range:
Function:
0 A
[0 - par.
Enter the I
*
LOW
H-71 A]
falls below this limit, the display reads Current
Low. The signal outputs can be programmed to
produce a status signal on terminal 27 or 29
and on relay output 01 or 02. Refer to
Illustration 3.32.
H-71 Warning Current High
Range:
Function:
par.
[par. H-70
Enter the I
DR-37 A
- par.
current exceeds this limit, the display
*
DR-37 A]
reads Current High. The signal outputs
can be programmed to produce a status
signal on terminal 27 or 29 and on relay
output 01 or 02. Refer to Illustration 3.32.
H-72 Warning Speed Low
Range:
Function:
0 RPM
[0 - par.
Enter the n
*
H-73 RPM]
speed exceeds this limit, the display reads
Speed low. The signal outputs can be
programmed to produce a status signal on
terminal 27 or 29 and on relay output 01 or
02.
DET-618D
AF-650 GP™ Programming Guide
value. When the motor current
value. When the motor
HIGH
value. When the motor
LOW
02/2016 All rights reserved.
H-73 Warning Speed High
Range:
Function:
3600
[par. H-72
Enter the n
RPM
- 60000
speed exceeds this value, the display reads
*
RPM]
Speed high. The signal outputs can be
programmed to produce a status signal on
terminals 27 or 29 and on relay outputs 01
or 02. Refer to Illustration 3.32.
H-74 Warning Reference Low
Range:
-999999.999
[-999999.999 -
*
par. H-75]
H-75 Warning Reference High
Range:
Function:
999999.999
[par. H-74 -
Enter the upper reference limit.
*
999999.999]
When the actual reference exceeds
this limit, the display reads Ref
The signal outputs can be
programmed to produce a status
signal on terminal 27 or 29 and
on relay output 01 or 02.
H-76 Warning Feedback Low
Range:
-999999.999
[-999999.999 -
ReferenceFeed-
par. H-77
backUnit
ReferenceFeed-
*
backUnit]
H-77 Warning Feedback High
Range:
999999.999
[par. H-76 -
ReferenceFeed-
999999.999
backUnit
ReferenceFeed-
*
backUnit]
value. When the motor
HIGH
Function:
Enter the lower reference limit.
When the actual reference drops
below this limit, the display
indicates Ref
. The signal
LOW
outputs can be programmed to
produce a status signal on
terminal 27 or 29 and on relay
output 01 or 02.
.
high
Function:
Enter the lower feedback
limit. When the feedback
drops below this limit,
the display reads
Feedb
. The signal
Low
outputs can be
programmed to produce
a status signal on
terminal 27 or 29 and on
relay output 01 or 02.
Function:
Enter the upper feedback
limit. When the feedback
exceeds this limit, the
display reads Feedb
.
High
The signal outputs can
be programmed to
produce a status signal
on terminal 27 or 29 and
on relay output 01 or 02.
75
3
3