2.1.4 Error Codes
Error codes
Error Code 00
is issued after power up or after a time out where all overridden points were released, as long as no Identify yourself command
has been issued by the master.
Error Code 01
is issued if the command is not supported or not known by the drive.
Error Code 02
is issued if the received message has a checksum error.
Error Code 03
is issued if the N2 message receive buffer exceeds 256 characters.
Error Code 05
is issued if the received N2 message is too long.
Error Code 10
is issued the data is out of expected range
Error Code 11
is issued when:
1. A point attributes or attribute bit is unused.
2. A point attributes or attribute bit is for JCI use only.
3. An internal data point attribute for current value can not be changed while running
Error Code 12
is issued when:
1. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is tripped.
2. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is trip locked except for BO 5 "reset"

2.1.5 Drive Parameters

The following parameters may need to be manually set for each drive in the Metasys N2 network. Refer to the Installation, Operation and Maintenance Manual
for the frequency converter for programming.
Parameter list
DRIVEPARAMETER
O-01
O-02
O-03
O-30
O-31
O-32
O-33
O-37
DESCRIPTION
DEFAULT
Control Side
Digital & Ctrl. Word
Control Source
Drive Port
Control Word Timeout
60 s
Protocol
Drive
Address
1
Drive Port Baud Rate
9600
Drive Port Parity
Even, 1stop
Maximum Inter-char Delay
AF-600 FP Metasys
DESIRED SETTING
Drive Port
1-18000 s
Metasys N2
1-255
Fixed to 9600
Fixed to No Parity, 1stop
25 s for Metasys N2
2
7