Ec-## Feedback Option - GE AF-650 GP Programming Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions

3.14 EC-## Feedback Option

3.14.1 EC-1# Inc. Enc. Interface
EC-10 Signal Type
3
3
Select the incremental type (A/B channel) of the encoder in use.
Find the information on the encoder datasheet.
Select [0] None if the feedback sensor is an absolute encoder
only.
Option:
[0]
[1]
*
[2]
EC-11 Resolution (PPR)
Range:
1024
[10 - 10000] Enter the resolution of the incremental
*
3.14.2 EC-2# Abs. Enc. Interface
EC-20 Protocol Selection
Option:
[0]
None
*
[1]
HIPERFACE Select [1] HIPERFACE if the encoder is absolute
[2]
EnDat
[4]
SSI
EC-21 Resolution (Positions/Rev)
Range:
8192
[4 -
*
131072]
EC-24 SSI Data Length
Range:
13
[13 - 25] Set the number of bits for the SSI telegram.
*
120
Function:
None
RS422 (5V TTL)
Sinusoidal 1Vpp
Function:
track, that is, the number of pulses or
periods per revolution.
Function:
NOTICE
This parameter cannot be adjusted while
the motor runs.
Select [0] None if the feedback sensor is an
incremental encoder only.
only.
Function:
Select the resolution of the absolute
encoder, that is, the number of counts per
revolution.
The value depends on setting in
parameter EC-20 Protocol Selection.
Function:
Select 13 bits for single-turn encoders and 25
bits for multi-turn encoders.
EC-25 Clock Rate
Range:
260 kHz
[100 - 260
*
kHz]
EC-26 SSI Data Format
Option:
[0]
Gray code
*
[1]
Binary code
EC-34 HIPERFACE Baudrate
Option:
[0]
600
[1]
1200
[2]
2400
[3]
4800
[4]
9600
*
[5]
19200
[6]
38400
3.14.3 EC-6# Monitoring and App.
EC-60 Feedback Direction
Option:
[0]
Clockwise
*
[1]
Counter
clockwise
EC-61 Feedback Signal Monitoring
Select which reaction the frequency converter should take in
case a faulty encoder signal is detected.
The encoder function in parameter EC-61 Feedback Signal
Monitoring is an electrical check of the hardware circuit in the
encoder system.
Option:
[0]
[1]
*
02/2016 All rights reserved.
Function:
Set the SSI clock rate. With long
encoder cables, the clock rate must be
reduced.
Function:
Set the data format of the SSI data.
Function:
NOTICE
This parameter cannot be adjusted while the
motor runs.
Select the baud rate of the attached encoder.
The parameter is only accessible when
parameter EC-20 Protocol Selection is set to [1]
HIPERFACE.
Function:
NOTICE
This parameter cannot be adjusted
while the motor runs.
Change the detected encoder rotation
direction without changing the wiring to
the encoder.
Function:
Disabled
Warning
DET-618D