Parameter Descriptions
LC-42 Logic Rule Boolean 2
Array [6]
Option:
Function:
[0]
False Select the second boolean (TRUE or FALSE) input for
*
the selected logic rule. See parameter LC-01 Start
Event ([0] - [61]) and parameter LC-02 Stop Event ([70]
- [75]) for further description.
LC-43 Logic Rule Operator 2
Array [6]
Option:
Function:
Select the 2
the boolean input calculated in:
Parameter LC-40 Logic Rule Boolean
1.
Parameter LC-41 Logic Rule Operator
1.
Parameter LC-42 Logic Rule Boolean
2.
and the boolean input coming from
parameter LC-42 Logic Rule Boolean 2.
[LC-44] signifies the boolean input of
parameter LC-44 Logic Rule Boolean 3.
[LC-40/LC-42] signifies the boolean input
calculated in:
Parameter LC-40 Logic Rule Boolean
1.
Parameter LC-41 Logic Rule Operator
1.
Parameter LC-42 Logic Rule Boolean
2.
[0]
DISABLED
Select this option to ignore
*
parameter LC-44 Logic Rule Boolean 3.
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND
NOT
[8]
NOT OR NOT
LC-44 Logic Rule Boolean 3
Array [6]
Option:
Function:
[0]
False Select the third boolean (TRUE or FALSE) input for
*
the selected logic rule. See parameter LC-01 Start
Event ([0] - [61]) and parameter LC-02 Stop Event ([70]
- [75]) for further description.
DET-618D
AF-650 GP™ Programming Guide
nd
logical operator to be used on
02/2016 All rights reserved.
3.20.5 LC-5# States
Parameters to configure the Logic Controller (LC) states.
States define the events and actions to take place in the
drive.
LC-51 Logic Controller Event
Array [20]
Option:
Function:
[0]
False Select the boolean input (TRUE or FALSE) to define
*
the Logic Controller event.See parameter LC-01 Start
Event ([0] - [61]) and parameter LC-02 Stop Event ([70]
- [74]) for further description.
LC-52 Logic Controller Action
Option:
Function:
Select the action corresponding to the LC
event. Actions are executed when the
corresponding event (defined in
parameter LC-51 Logic Controller Event) is
evaluated as true.
[0]
DISABLED
*
[1]
No action
[2]
Select set-up 1 Changes the active set-up
(parameter K-10 Active Set-up) to 1.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a Network.
[3]
Select set-up 2 Changes the active set-up
parameter K-10 Active Set-up) to 2.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a Network.
[4]
Select set-up 3 Changes the active set-up
(parameter K-10 Active Set-up) to 3.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a Network.
[5]
Select set-up 4 Changes the active set-up
(parameter K-10 Active Set-up) to 4.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a Network.
[10] Select preset
Selects preset reference 0.
ref 0
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a Network.
[11] Select preset
Selects preset reference 1.
ref 1
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a Network.