Parameter Descriptions

3.7 H-## High Perf Parameters

Parameter group related to high performance functions in
the drive.
3.7.1 H-0# High Perf Operations
3
3
Parameters to restore factory setting, configure auto reset,
fan operation, reverse lock and start mode (catch a
spinning load).
H-01 Option Detection
Selects the behaviour of the frequency converter when a change
in the option configuration is detected.
Option:
[0]
Protect Option
*
Config.
[1]
Enable Option
Change
H-02 Option Data Storage
Range:
0
[0 - 65535]
*
H-03 Restore Factory Settings
Option:
[0]
Normal
*
operation
[2]
Restore
Factory
Settings
H-04 Auto-Reset (Times)
Option:
60
AF-650 GP Programming Guide
Function:
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
Changes drive settings and is used
when modifying the system configu-
ration. This Parameter setting will
return to [0] Protect Option Config.
after an Option Change.
Function:
Function:
Use this parameter to specify normal
operation, to perform tests or to restore all
parameters except ID-03 Power Up's,
ID-04 Over Temp's and ID-05 Over Volt's. This
function is active only when the power is
cycled (power off-power on) to the frequency
converter.
Select [0] Normal operation for normal
operation of the frequency converter with the
motor in the selected application.
Select [2] Restore Factory Settings to reset all
parameter values to default settings, except
for ID-03 Power Up's, ID-04 Over Temp's and
ID-05 Over Volt's. The frequency converter will
reset during the next power-up.
H-03 Restore Factory Settings will also revert to
the default setting [0] Normal operation.
Function:
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
H-04 Auto-Reset (Times)
Option:
[0]
Manual reset
*
[1]
Automatic reset x 1
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] Automatic reset x 10
[11] Automatic reset x 15
[12] Automatic reset x 20
[13] Infinite auto reset
NOTE
The motor may start without warning. If the specified
number of AUTOMATIC RESETs is reached within 10
minutes, the frequency converter enters Manual reset [0]
mode. After the Manual reset is performed, the setting of
H-04 Auto-Reset (Times) reverts to the original selection. If
the number of automatic resets is not reached within 10
minutes, or when a Manual reset is performed, the internal
AUTOMATIC RESET counter returns to zero.
H-05 Auto-Reset (Reset Interval)
Range:
Function:
10 s
[0 - 600 s] Enter the time interval from trip to start of
*
the automatic reset function. This parameter
is active when H-04 Auto-Reset (Times) is set
to [1] - [13] Automatic reset.
H-07 Accel/Decel Time 1 Type
Option:
Function:
Select the ramp type, depending on
requirements for acceleration/deceleration.
A linear ramp will give constant acceleration
during ramping. An S-ramp will give non-
linear acceleration, compensating for jerk in
the application.
[0]
Linear
*
[1]
S-ramp Const
Acceleration with lowest possible jerk.
Jerk
[2]
S-ramp Const
S-ramp based on the values set in F-07 Accel
Time
Time 1 and F-08 Decel Time 1.
DET-618C
Function:
Select [0] Manual reset, to perform a
reset via [RESET] or via the digital
inputs.
Select Automatic reset x 1...x20 [1]-
[12] to perform between one and
twenty automatic resets after
tripping.
Select [13] Infinite Automatic Reset for
continuous resetting after tripping.