How to Program
2.1.15 Readout and Programming of
Indexed Parameters
2
2
Parameters are indexed when placed in a rolling stack.
Parameter ID-30 Fault Log: Error Code to
parameter ID-32 Alarm Log: Time contain a fault log, which
can be read out. Select a parameter, press [OK], and press
the keys [
] [
For example, parameter C-05 Multi-step Frequency 1 - 8 is
changed as follows:
1.
Select the parameter, press [OK], and press [
to scroll through the indexed values.
2.
To change the parameter value, select the
indexed value and press [OK].
3.
Change the value by pressing [
4.
Press [OK] to accept the new setting.
5.
Press [Cancel] to abort. Press [Back] to leave the
parameter.

2.1.16 Local Control Keys

Keys for local control are at the bottom of the keypad.
Illustration 2.20 Keypad Keys
[Hand]
Enables control of the frequency converter via the keypad.
[Hand] also starts the motor and it is now possible to enter
the motor speed data with the navigation keys. The key
can be selected as [1] Enable or [0] Disable via
parameter K-40 [Hand] Button on Keypad.
External stop signals activated with control signals, or a
fieldbus, override a start command via the keypad.
The following control signals are still active when [Hand] is
activated:
[Hand] - [Off] - [Auto].
Reset.
Coast stop inverse.
Reversing.
Set-up select lsb - Set-up select msb.
Stop command from serial communication.
Quick stop.
22
] to scroll through the value log.
] [
[Off]
Stops the connected motor. The key can be selected as [1]
Enable or [0] Disable via parameter K-41 [Off] Button on
Keypad.
If no external stop function is selected and the [Off] key is
inactive, the motor can be stopped by disconnecting the
voltage.
[Auto]
Enables control of the frequency converter via the control
terminals and/or serial communication. When a start signal
is applied on the control terminals and/or the bus, the
] [
]
frequency converter starts. The key can be selected as [1]
Enable or [0] Disable via parameter K-42 [Auto] Button on
Keypad.
NOTICE
].
An active HAND-OFF-AUTO signal via the digital inputs
has higher priority than the control keys [Hand] and
[Auto].
[Reset]
Is used for resetting the frequency converter after an alarm
(trip). It can be selected as [1] Enable or [0] Disable via
parameter K-43 [Reset] Button on Keypad.
2.1.17 Restoring Drive to Factory Settings
The drive can be restored to factory settings in 2 ways.
Recommended
1.
2.
3.
4.
5.
6.
Parameter H-03 Restore Factory Settings restores all except:
02/2016 All rights reserved.
DC brake.
Select parameter H-03 Restore Factory Settings.
Press [OK].
Select [2] Restore Factory Settings.
Press [OK].
Disconnect the mains supply and wait until the
display turns off.
Reconnect the mains supply. The frequency
converter is now reset.
Parameter SP-50 RFI Filter.
Parameter O-30 Protocol.
Parameter O-31 Address.
Parameter O-32 Drive Port Baud Rate.
Parameter O-35 Minimum Response Delay.
Parameter O-36 Max Response Delay.
Parameter O-37 Max Inter-Char Delay.
Parameter ID-00 Operating hours to
parameter ID-05 Over Volt's.
Parameter ID-20 Historic Log: Event to
parameter ID-22 Historic Log: Time.