Parameter Descriptions

3.20 LC-## Logic Controller

Parameter group related to programming the drive's built-
in Logic Controller. The Logic Controller consists of a series
of user defined actions (see parameter LC-52 Logic
Controller Action) that are executed when the
corresponding user-defined events are met.
3.20.1 LC-0# LC Settings
Parameters to configure the activation, deactivations and
reset of the Logic Controller (LC).
LC-00 Logic Controller Mode
Option:
Function:
[0]
Off
Disables the logic controller.
*
[1]
On
Enables the logic controller.
LC-01 Start Event
Select the boolean (true or false) input to activate Logic
Controller.
Option:
Function:
[0]
False
Select the boolean (true or false) input
to activate Logic Controller.
Enters the fixed value - false.
[1]
True
Enters the fixed value - true.
[2]
Running
The motor runs.
[3]
In range
The motor runs within the programmed
current and speed ranges set in
parameter H-70 Warning Current Low to
parameter H-73 Warning Speed High.
[4]
On reference
The motor runs on reference.
[5]
Torque limit
The torque limit set in
parameter F-40 Torque Limiter (Driving) or
parameter F-41 Torque Limiter (Braking) is
exceeded.
[6]
Current Limit
The motor current limit set in
parameter F-43 Current Limit is exceeded.
[7]
Out of current
The motor current is outside the range
range
set in parameter F-43 Current Limit.
[8]
Below I low
The motor current is lower than set in
parameter H-70 Warning Current Low.
[9]
Above I high
The motor current is higher than set in
parameter H-71 Warning Current High.
[10]
Out of speed
The speed is outside the range set in
range
parameter H-72 Warning Speed Low and
parameter H-73 Warning Speed High.
[11]
Below speed
The output speed is lower than the
low
setting in parameter H-72 Warning Speed
Low.
DET-618D
AF-650 GP™ Programming Guide
LC-01 Start Event
Select the boolean (true or false) input to activate Logic
Controller.
Option:
[12]
Above speed
high
[13]
Out of feedb.
range
[14]
Below feedb.
low
[15]
Above feedb.
high
[16]
Thermal
warning
[17]
Line voltage out
of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock) A (trip lock) alarm is active.
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[33]
Digital input
DI18
[34]
Digital input
DI19
[35]
Digital input
DI27
[36]
Digital input
DI29
[37]
Digital input
DI32
[38]
Digital input
DI33
[39]
Start command
*
02/2016 All rights reserved.
Function:
The output speed is higher than the
setting in parameter H-73 Warning Speed
High.
The feedback is outside the range set in
parameter H-76 Warning Feedback Low
and parameter H-77 Warning Feedback
High.
The feedback is below the limit set in
parameter H-76 Warning Feedback Low.
The feedback is above the limit set in
parameter H-77 Warning Feedback High.
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the
brake resistor, or the thermistor.
The mains voltage is outside the
specified voltage range.
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
"running" AND "reverse").
A warning is active.
A (trip) alarm is active.
Use the result of comparator 0.
Use the result of comparator 1.
Use the result of comparator 2.
Use the result of comparator 3.
Use the result of logic rule 0.
Use the result of logic rule 1.
Use the result of logic rule 2.
Use the result of logic rule 3.
Use the result of digital input 18.
Use the result of digital input 19.
Use the result of digital input 27.
Use the result of digital input 29.
Use the result of digital input 32.
Use the result of digital input 33.
A start command is issued.