Parameter Descriptions
LC-10 Comparator Operand
Option:
3
3
[181] Remote
reference active
[182] Start command
[183] Drive stopped
[185] Drive in hand
mode
[186] Drive in auto
mode
[187] Start command
given
[190] Digital input
x30/2
[191] Digital input
x30/3
[192] Digital input
x30/4
LC-11 Comparator Operator
Array [6]
Option:
[0]
<
[1]
≈ (equal)
*
[2]
>
[5]
TRUE
longer
than..
[6]
FALSE
longer
than..
140
Function:
parameter F-02 Operation Method is [0]
Linked to hand Auto, at the same time as
the keypad is in hand mode.
Active when parameter F-02 Operation
Method is [1] Remote or [0] Linked to
hand/auto, while the keypad is in auto
mode.
Active when there is an active start
command, and no stop command.
A stop command (jog, stop, qstop, coast)
is issued – and not from the Logic
Controller itself.
Active when the frequency converter is
in hand on mode.
Active when the frequency converter is
in auto mode.
Function:
Select [0] < for the result of the evaluation to
be TRUE, when the variable selected in
parameter LC-10 Comparator Operand is smaller
than the fixed value in
parameter LC-12 Comparator Value. The result is
FALSE, if the variable selected in
parameter LC-10 Comparator Operand is greater
than the fixed value in
parameter LC-12 Comparator Value.
Select [1] ≈ for the result of the evaluation to
be TRUE, when the variable selected in
parameter LC-10 Comparator Operand is approxi-
mately equal to the fixed value in
parameter LC-12 Comparator Value.
Select [2] > for the inverse logic of option [0] <.
LC-11 Comparator Operator
Array [6]
Option:
[7]
TRUE
shorter
than..
[8]
FALSE
shorter
than..
LC-12 Comparator Value
Array [6]
Range:
0
[-100000 -
*
100000]
LC-15 RS-FF Operand S
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Line voltage out of range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
Logic Controller Time-out 0
[31]
Logic Controller Time-out 1
[32]
Logic Controller Time-out 2
[33]
Digital input DI18
02/2016 All rights reserved.
Function:
Function:
Enter the trigger level for the variable that
is monitored by this comparator. This is an
array parameter containing comparator
values 0–5.
Function:
DET-618D