GE AF-650 GP Programming Manual page 55

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
E-81 Term 32/33 Encoder Direction
Option:
3
3
[0]
Clockwise
*
[1]
Counter
clockwise
3.4.7 E-9# Bus Controlled
Parameters to configure digital, relay and pulse train
outputs to be controlled by the serial communications.
E-90 Digital & Relay Bus Control
Range:
0
[0 - 2147483647] This parameter holds the state of the
*
Bit 0
Digital Output Terminal 27
Bit 1
Digital Output Terminal 29
Bit 2
Digital Output Terminal X 30/6
Bit 3
Digital Output Terminal X 30/7
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9–31
Reserved for future terminals
Table 3.11 Bus-controlled Digital Outputs and Relays
E-93 Pulse Out #27 Bus Control
Range:
0 %
[0 -
*
100 %]
54
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to the
encoder.
Sets channel A 90° (electrical degrees)
behind channel B upon clockwise rotation of
the encoder shaft.
Sets channel A 90° (electrical degrees) ahead
of channel B upon clockwise rotation of the
encoder shaft.
Function:
digital outputs and relays that is
controlled by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is
low or inactive.
Function:
Set the output frequency transferred to
output terminal 27 when the terminal is
configured as [45] Bus Controlled in
parameter E-70 Terminal 27 Pulse Output
Variable.
02/2016 All rights reserved.
E-94 Pulse Out #27 Timeout Preset
Range:
Function:
0 %
[0 -
Set the output frequency transferred to output
*
100 %]
terminal 27 when the terminal is configured as
[48] Bus Ctrl Timeout in parameter E-70 Terminal
27 Pulse Output Variable and a timeout is
detected.
E-95 Pulse Out #29 Bus Control
Range:
Function:
0 %
[0 -
Set the output frequency transferred to
*
100 %]
output terminal 29 when the terminal is
configured as [45] Bus Controlled in
parameter E-73 Terminal 29 Pulse Output
Variable.
E-96 Pulse Out #29 Timeout Preset
Range:
Function:
0 %
[0 -
Set the output frequency transferred to output
*
100 %]
terminal 29 when the terminal is configured as
[48] Bus Ctrl Timeout in parameter E-73 Terminal
29 Pulse Output Variable and a timeout is
detected.
E-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0 %
[0 -
Set the output frequency transferred to
*
100 %]
output terminal X30/6 when the terminal is
configured as [45] Bus ctrl. in
parameter E-76 Terminal X30/6 Pulse Output
Variable.
E-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0 %
[0 -
Set the output frequency transferred to output
*
100 %]
terminal X30/6 when the terminal is configured
as [48] Bus Ctrl Timeout in
parameter E-76 Terminal X30/6 Pulse Output
Variable and a timeout is detected.