Parameter Descriptions
[1266] Digital Output
Binary value of all digital outputs.
[bin]
[1267] Freq. Input #29
Actual value of the frequency applied
[Hz]
at terminal 29 as an impulse input.
[1268] Freq. Input #33
Actual value of the frequency applied
[Hz]
at terminal 33 as an impulse input.
[1269] Pulse Output
Actual value of impulses applied to
#27 [Hz]
terminal 27 in digital output mode.
[1270] Pulse Output
Actual value of impulses applied to
#29 [Hz]
terminal 29 in digital output mode.
[1271] Relay Output
[bin]
[1272] Counter A
Application dependent (e.g. LC Control)
[1273] Counter B
Application dependent (e.g. LC Control)
[1274] Prec. Stop
Display the actual counter value.
Counter
[1275] Analog input
Actual value at input X30/11 either as
X30/11
reference or protection value.
[1276] Analog input
Actual value at input X30/12 either as
X30/12
reference or protection value.
[1277] Analog output
Actual value at output X30/8 in mA.
X30/8 mA
Use parameter AN-60 Terminal X30/8
Output to select the value to be shown.
[1280] Fieldbus CTW 1
Control word (CTW) received from the
Bus Master.
[1282] Fieldbus REF 1
Main reference value sent with control
word from the Bus Master.
[1284] Comm. Option
Extended network communication
STW
option status word.
[1285] Drive Port CTW
Control word (CTW) received from the
1
Bus Master.
[1286] Drive Port REF 1
Status word (STW) sent to the Bus
Master.
[1290] Alarm Word
One or more alarms in a Hex code.
[1291] Alarm Word 2
One or more alarms in a Hex code.
[1292] Warning Word
One or more warnings in a Hex code.
[1293] Warning Word 2
One or more warnings in a Hex code.
[1294] Ext. Status Word
One or more status conditions in a Hex
code.
[1295] Ext. Status Word
One or more status conditions in a Hex
2
code.
K-20 Display Line 1.1 Small
Option: Function:
Select a variable for display in line 1, left position. The
options are the same as listed for parameter group
K-2#.
K-21 Display Line 1.2 Small
Option: Function:
Select a variable for display in line 1, middle position.
The options are the same as listed for parameter group
K-2#.
DET-618D
AF-650 GP™ Programming Guide
K-22 Display Line 1.3 Small
Option: Function:
K-23 Display Line 2 Large
Option: Function:
K-24 Display Line 3 Large
Select a variable for display in line 3.
K-25 Quick Start
Array [50]
Define up to 50 parameters to appear in the Quick Start Menu,
accessible via the [Quick Menu] key on the keypad. The
parameters are displayed in the Quick Start Menu in the order
they are programmed into this array parameter. Delete
parameters by setting the value to 0000.
For example, this can be used to provide quick, simple access to
just one or up to 50 parameters which require changing on a
regular basis (for example for plant maintenance reasons) or by
an OEM to enable simple commissioning of their equipment.
Range:
0
[0 - 9999] Define up to 50 parameters to appear in the
*
3.2.4 K-3# Keypad Custom Readout
It is possible to customize the display elements for various
purposes: *Custom Readout. Value proportional to speed
(Linear, squared or cubed depending on unit selected in
parameter K-30 Unit for Custom Readout) *Display Text. Text
string stored in a parameter.
Custom Readout
The calculated value to be displayed is based on settings
in parameter K-30 Unit for Custom Readout,
parameter K-31 Min Value of Custom Readout (linear only),
parameter K-32 Max Value of Custom Readout,
parameter F-17 Motor Speed High Limit [RPM],
parameter F-15 Motor Speed High Limit [Hz] and actual
speed.
02/2016 All rights reserved.
Select a variable for display in line 1, right position. The
options are the same as listed for parameter group
K-2#.
Select a variable for display in line 2. The options are
the same as those listed for parameter group K-2#.
Function:
Quick Start Menu, accessible via the [Quick Menu]
key on the keypad. The parameters are displayed
in the Quick Start Menu in the order they are
programmed into this array parameter. Delete
parameters by setting the value to '0000' .
For example, this can be used to provide quick,
simple access to just 1 or up to 50 parameters
which require changing on a regular basis (e.g.
for plant maintenance reasons) or by an OEM to
enable simple commissioning of their equipment.
3
3
29