How To Access Parameters; Parameter Handling; Storage Of Data; Ind - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

RS485 Installation and Set-...
Coil
0
33
Control not ready
34
Frequency converter not
ready
35
Coasting stop
36
No alarm
37
Not used
38
Not used
39
Not used
40
No warning
41
Not at reference
42
Hand mode
43
Out of freq. range
44
Stopped
45
Not used
46
No voltage warning
47
Not in current limit
48
No thermal warning
Table 9.10 Frequency Converter Status Word (Drive Profile)
Register
Description
number
00001–00006 Reserved
00007
Last error code from an Drive data object
interface
00008
Reserved
00009
Parameter index*
00010–00990 000 parameter group (parameters 001 through
099)
01000–01990 100 parameter group (parameters 100 through
199)
02000–02990 200 parameter group (parameters 200 through
299)
03000–03990 300 parameter group (parameters 300 through
399)
04000–04990 400 parameter group (parameters 400 through
499)
...
...
49000–49990 4900 parameter group (parameters 4900 through
4999)
50000
Input data: Frequency converter control word
register (CTW).
50010
Input data: Bus reference register (REF).
...
...
50200
Output data: Frequency converter status word
register (STW).
50210
Output data: Frequency converter main actual
value register (MAV).
Table 9.11 Holding Registers
* Used to specify the index number to be used when accessing an
indexed parameter.
MG35M402
AF-650 GP™ Design and Installation Guide
1
Control ready
Frequency converter ready
Safety closed
Alarm
Not used
Not used
Not used
Warning
At reference
Auto mode
In frequency range
Running
Not used
Voltage warning
Current limit
Thermal warning
DET-767c All rights reserved.

9.2.4 How to Access Parameters

9.2.4.1 Parameter Handling

The PNU (Parameter Number) is translated from the
register address contained in the Modbus read or write
message. The parameter number is translated to Modbus
as (10 x parameter number) DECIMAL.
All parameters are named with one or two letters, a "-" and
a number for example, F-07. To access parameters, use
Table 9.12 because letters cannot be addressed.
Example: F-07=7, E-01=101, DR-53=1253.
Letter
F
E
C
P
H
K
AN
B
O
PB
SP
DR
ID
DN
PI
LC
EC
RS
EN
Table 9.12

9.2.4.2 Storage of Data

The Coil 65 decimal determines whether data written to
the frequency converter are stored in EEPROM and RAM
(coil 65=1) or only in RAM (coil 65=0).

9.2.4.3 IND

The array index is set in Holding Register 9 and used when
accessing array parameters.

9.2.4.4 Text Blocks

Parameters stored as text strings are accessed in the same
way as the other parameters. The maximum text block size
is 20 characters. If a read request for a parameter is for
more characters than the parameter stores, the response is
truncated. If the read request for a parameter is for fewer
characters than the parameter stores, the response is space
filled.
Number
0
1
2
3
4
5
6
7
8
9
10
12
15
22
23
24
25
26
29
91
9
9

Advertisement

Table of Contents
loading

Table of Contents