Parameter Descriptions
SP-55 Output Filter
Option:
Function:
NOTICE
This parameter cannot be adjusted while the
motor is running.
NOTICE
Reset the frequency converter after selecting
[2] Sine-Wave Filter Fixed.
CAUTION
OVERHEATING OF FREQUENCY
CONVERTER
Always set parameter SP-55 Output Filter to
[2] Sine-wave fixed when using a sine-wave
filter. Failure to do so can result in
overheating of the frequency converter,
which can result in personal injury and
equipment damage.
Select if a sine-wave output filter connected.
[0]
No
This is the default setting and should be used with
Filter
dU/dt filters or high frequency common mode (HF-
*
CM) filters.
[1]
Sine-
This setting is only for backwards compatibility. It
Wave
enables operation with flux control principle when
Filter
parameter SP-56 Capacitance Output Filter and
parameter SP-57 Inductance Output Filter are
programmed with the output filter capacitance and
inductance. It does not limit the range of the
switching frequency.
[2]
Sine-
This parameter sets a minimum allowed limit to the
Wave
switching frequency and ensures that the filter is
Filter
operated within the safe range of switching
Fixed
frequencies. Operation is possible with all control
principles. For flux control principle, program
parameter SP-56 Capacitance Output Filter and
parameter SP-57 Inductance Output Filter (these
parameters have no effect in Advanced Vector
Control and U/f). The modulation pattern is set to
SFAVM, which gives the lowest acoustic noise in the
filter.
DET-618D
AF-650 GP™ Programming Guide
SP-56 Capacitance Output Filter
Range:
2.0 uF
*
SP-57 Inductance Output Filter
Range:
7.000
mH
*
SP-59 Actual Number of Inverter Units
Range:
1
[1 - 1]
*
3.9.6 SP-7# Additional ADD/DEC Settings
Parameters to configure the jerk compensations for S-
Ramps settings on Accel/Decel Ramps 1 through 4.
For each of four ramps (parameter groups F-0#, E-1#, H-0#,
SP-7#, SP-8# and SP-9#) configure the ramp parameters:
ramp type, ramping times (duration of acceleration and
deceleration) and level of jerk compensation for S ramps.
Start by setting the linear ramping times corresponding to
the figures.
If S-ramps are selected then set the level of non-linear jerk
compensation required. Set jerk compensation by defining
the proportion of ramp-up and ramp-down times where
acceleration and deceleration are variable (i.e. increasing or
decreasing). The S-ramp acceleration and deceleration
settings are defined as a percentage of the actual ramp
time.
SP-71 Accel Time 1 S-ramp Ratio at Accel. Start
Range:
50 %
*
99 %]
02/2016 All rights reserved.
Function:
[0.1 -
Set the capacitance of the output filter. The
6500 uF]
value can be found on the filter label.
NOTICE
This is required for correct compen-
sation in Flux mode
(parameter H-41 Motor Control
Principle)
Function:
[0.001 -
Set the inductance of the output filter.
65 mH]
The value can be found on the filter label.
NOTICE
This is required for correct compen-
sation in Flux mode
(parameter H-41 Motor Control
Principle)
Function:
Set the actual number of power units.
Function:
[1 -
Enter the proportion of the total accel time
(parameter F-07 Accel Time 1) in which the
acceleration torque increases. The larger the
percentage value, the greater the jerk
3
3
93