Parameter Descriptions
3.24.3 IO-2# Analog Input X49/3
IO-20 Terminal X49/3 Low Voltage
Range:
Function:
0.07 V
[0 - par.
Enter the voltage (V) that corresponds to
*
IO-22 V]
the low reference value (set in
parameter IO-24 Term. X49/3 Low Ref./
Feedb. Value).
IO-21 Terminal X49/3 Low Current
Range:
Function:
4 mA
[0 - par.
Enter the current (mA) that corresponds
*
IO-23 mA]
to the low reference value (set in
parameter IO-24 Term. X49/3 Low Ref./
Feedb. Value).
IO-22 Terminal X49/3 High Voltage
Range:
Function:
10 V
[par. IO-20 -
Enter the voltage (V) that corresponds to
*
10 V]
the high reference value (set in
parameter IO-25 Term. X49/3 High Ref./
Feedb. Value).
IO-23 Terminal X49/3 High Current
Range:
Function:
20 mA
[par. IO-21 -
Enter the current (mA) that corresponds
*
20 mA]
to the high reference value (set in
parameter IO-25 Term. X49/3 High Ref./
Feedb. Value).
IO-24 Term. X49/3 Low Ref./Feedb. Value
Range:
Function:
0
[-999999.999 -
Enter the reference or feedback value (in
*
999999.999]
RPM, Hz, bar, etc.) that corresponds to the
voltage or current set in
parameter IO-20 Terminal X49/3 Low
Voltage/parameter IO-21 Terminal X49/3
Low Current.
IO-25 Term. X49/3 High Ref./Feedb. Value
Range:
Function:
100
[-999999.999 -
Enter the reference or feedback value (in
*
999999.999]
RPM, Hz, bar, etc.) that corresponds to
the voltage or current set in
parameter IO-22 Terminal X49/3 High
Voltage/parameter IO-23 Terminal X49/3
High Current.
IO-26 Term. X49/3 Filter Time Constant
Range:
Function:
0.001 s
[0.001 - 10
Enter the filter time constant. This is a
*
s]
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X49/3. A high time constant
DET-618D
AF-650 GP™ Programming Guide
IO-26 Term. X49/3 Filter Time Constant
Range:
IO-27 Term. X49/3 Live Zero
This parameter gives the possibility of disabling live zero
monitoring. E.g. for use as decentral I/O.
Option:
[0]
[1]
*
3.24.4 IO-3# Analog Input X49/5
IO-30 Terminal X49/5 Low Voltage
Range:
0.07 V
*
IO-31 Terminal X49/5 Low Current
Range:
4 mA
*
IO-32 Terminal X49/5 High Voltage
Range:
10 V
*
10 V]
IO-33 Terminal X49/5 High Current
Range:
20 mA
*
IO-34 Term. X49/5 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999]
02/2016 All rights reserved.
Function:
value improves dampening but also
increases the delay through the filter.
Disabled
Enabled
Function:
[0 - par.
Enter the voltage (V) that corresponds to
IO-32 V]
the low reference value (set in
parameter IO-34 Term. X49/5 Low Ref./
Feedb. Value).
Function:
[0 - par.
Enter the current (mA) that corresponds
IO-33 mA]
to the low reference value (set in
parameter IO-34 Term. X49/5 Low Ref./
Feedb. Value).
Function:
[par. IO-30 -
Enter the voltage (V) that corresponds to
the high reference value (set in
parameter IO-35 Term. X49/5 High Ref./
Feedb. Value).
Function:
[par. IO-31 -
Enter the current (mA) that corresponds
20 mA]
to the high reference value (set in
parameter IO-35 Term. X49/5 High Ref./
Feedb. Value).
Function:
Enter the reference or feedback value (in
RPM, Hz, bar, etc.) that corresponds to the
voltage or current set in
parameter IO-20 Terminal X49/3 Low
Voltage/parameter IO-21 Terminal X49/3
Low Current.