Figure 5-27 Removing the access actuator
Step 4 Install the reserved access actuator in the original position and connect the cables.
Step 5 Synchronize the parameters of the access actuator on the ECC800 WebUI.
Step 6 Log in to the ECC800 WebUI and choose System Settings > Access Management. Set the
access permission for the new access actuator according to the access permission setting for
the old access actuator. Then perform Synchronize Permission.
Step 7 On the ECC800 WebUI, choose Monitoring > System > ECC800 > Controls > Delete
device with communication failure, and click Submit.
Step 8 Log in to the ECC800 WebUI, and edit the plan view by adding new devices.
Step 9 Verify that the aisle access control system is normal.
----End

5.4.3.2 Replacing an Access Control Device

The replacement methods are the same for the fingerprint and card reader with a keypad,
fingerprint and card reader, and card reader with a keypad.
Impact on the System
The access control system cannot be used.
Preparations
Procedure
Step 1 Remove screws from the bottom of the access control device and remove the access control
device from the baseplate.
Issue 04 (2020-01-03)
Tools: ESD wrist strap, ESD gloves, flat-head screwdriver, Phillips screwdriver, labels,
marker
Material: access control device