Replacing A Door Status Sensor - Huawei FusionModule2000 V500R003C10 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000 V500R003C10:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 5-39 Adjusting the gap
----End

5.4.3.6 Replacing a Door Status Sensor

Impact on the System
The cabinet door status cannot be detected.
Preparations
Procedure
Step 1 Remove the cover of the door status sensor manually.
Step 2 Remove the communications cable using a Phillips screwdriver and apply insulation measures
such as wrapping the cable with insulation tape to avoid hazards.
Step 3 Remove the door status sensor from the rack top using the Phillips screwdriver, as shown in
Figure
Issue 04 (2020-01-03)
Tools: Phillips screwdriver, insulation tape
Material: door status sensor
5-40.