FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 5-32 Removing the mounting plate of a magnetic lock cover
Step 2 Remove the cables for the double-door magnetic lock from the Phoenix terminal block on the
upper frame mounting kit.
Step 3 Replace the magnetic lock. Remove the magnetic lock from the fixing plate using the
delivered hex key, as shown in
Figure 5-33 Removing a magnetic lock
Step 4 Connect the magnetic lock cable to the new magnetic lock, and secure the magnetic lock to
the fixing plate using the delivered hex key, as shown in
Issue 04 (2020-01-03)
Figure
Copyright © Huawei Technologies Co., Ltd.
5-33.
Figure
5 Parts Replacement
5-34.