FusionModule2000 Smart Modular Data Center
Maintenance Guide
Step 8 Connect cables from the power connector to the AC actuator, and route the cables.
Figure 5-70 Connecting cables to a power connector (BOM number: 14190892)
Figure 5-71 Connecting cables to a power connector (BOM number: 14190242)
Step 9 Secure the pad power connector holder.
1.
2.
Issue 04 (2020-01-03)
Remove the baffle plate from the power connector mounting holes in the door box.
Secure the pad power connector holder to the door box using two M4x12 screw
assemblies.
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
110