Replacing An Alarm Beacon - Huawei FusionModule2000 V500R003C10 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000 V500R003C10:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 5-56 Connecting a conversion cable to a water detector
Step 2 Replace a water detection cable.
1.
2.
Figure 5-57 Connecting a new water detection cable
(1) Conversion cable end B, connecting to
the water detection cable
Step 3 Check whether the new water detector works properly. Connect the network cable between
the water detector and ECC, immerse the water detection cable in water, and check whether
an alarm is generated. If an alarm is generated, the replacement is complete.
Step 4 Wipe dry the water detection cable. The alarm automatically disappears.
----End

5.4.13 Replacing an Alarm Beacon

Impact on the System
No sound or flash can be generated by the alarm.
Issue 04 (2020-01-03)
Remove the faulty water detection cable from the port.
Install a new water detection cable.
The water detection cable and conversion cable are interconnected through the male and female
connectors.
Copyright © Huawei Technologies Co., Ltd.
(2) Water detection rope end A, connecting
to the conversion cable
5 Parts Replacement
100

Advertisement

Table of Contents
loading

Table of Contents