3.4 Quarterly Maintenance

Table 3-5 Quarterly maintenance for the power supply and distribution system
Item
Operating
temperature and
humidity of the
PDC
Table 3-6 Quarterly maintenance for the cooling system
Item
Monitoring
Electric heater
Wet film
humidifier
Issue 04 (2020-01-03)
Operation
Operation
Choose
Monitoring >
Power
Distribution on
the ECC800
WebUI.
Operation
Check the active
alarms.
Start the indoor
unit. Choose
Maint >
Diagnostic
Mode > Enter
on the main
screen, and set
Electric heater
to On.
NOTE
To avoid burns,
do not touch the
electric heater
surface with bare
skin.
Start the indoor
unit. Choose
Maint >
Diagnostic
Mode > Enter
Copyright © Huawei Technologies Co., Ltd.
Standard
Standard
Operating
temperature: –10° C
to +55° C
Humidity: 5%-95%
RH
Standard
There are no abnormal
records in alarms.
Check whether the
electric heater generates
heat.
Water drainage is
normal.
3 Routine Maintenance
Troubleshooting
indicator is steady
on, clear the alarm
by referring to the
iBattery User
Manual.
Troubleshooting
Check whether the data
center smart cooling
products and
dehumidifier in the
equipment room run
properly.
Troubleshooting
Rectify the fault or
contact Huawei
technical support.
Replace the electric
heater.
If no water is
supplied, check the
cable connection or
replace the water
24