Replacing An Rpdu; Replacing A Smart Rpdu - Huawei FusionModule2000 V500R003C10 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000 V500R003C10:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide

5.2.4 Replacing an rPDU

Impact on the System
One power input of the equipment cannot work.
Preparations
Context
Procedure
Step 1 Open the rear door of the cabinet.
Step 2 Connect the IT load of the faulty rPDU to a normal rPDU.
Step 3 Turn off the upstream power distribution switch for the faulty rPDU. Ensure that the rPDU
input has no power, and then remove the power cables from the terminal block on the top of
the rPDU.
Step 4 Remove the bolts that secure the rPDU using a Phillips screwdriver.
Step 5 Secure the new rPDU in the installation position of the old rPDU.
Step 6 Connect the input power cables to the rPDU.
Step 7 Turn on the upstream power distribution switch for the rPDU and the rPDU input switch.
Step 8 Verify that the rPDU power output is normal and then connect the IT load cables to the rPDU.
----End

5.2.5 Replacing a Smart rPDU

Impact on the System
One power input of the equipment cannot work.
Preparations
Context
The smart rPDU is installed near the rear door of the cabinet.
Issue 04 (2020-01-03)
Tools: Phillips screwdriver, step ladder
Material: rPDU of the same model that is available and functional
Skill requirement: power distribution engineers
The rPDU is installed near the rear door of the cabinet.
The rPDU has two types: vertical and horizontal. The following describes how to install
a vertical rPDU.
Tools: Phillips screwdriver, step ladder, label, marker
Material: smart rPDU of the same specifications