Monthly Maintenance - Huawei FusionModule2000 V500R003C10 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000 V500R003C10:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Check the smart
cooling product
status.
Check the power
supply and
distribution device
status.
Check the status
of the video
surveillance
system.

3.3 Monthly Maintenance

Table 3-2 Monthly maintenance for the power supply and distribution system
Item
UPS power grid
environment
Issue 04 (2020-01-03)
Operation Guide
On the ECC800
WebUI, choose
Monitoring >
Cooling.
On the ECC800
WebUI, choose
Monitoring > Power
Distribution.
Web Scenario:
Enter the IP
address of the
camera or use the
ECC800 to
monitor: System
Settings >
Cooling.
VCN Scenario:
Log in the IVS
client as the
Admin user,
choose Live
Feed > Cameras
for live video
browsing.
Operation
Check the
running status
on the UPS
LCD.
Copyright © Huawei Technologies Co., Ltd.
Standard
The smart cooling
product has
started.
Current
temperature:
18–27° C;
humidity:
20%–80%.
The power supply
and distribution
device is working
properly.
The video
surveillance system
is working properly.
Standard
Input voltage: 380
V AC/400 V
AC/415 V AC (line
voltage)
Output voltage:
380 V AC/400 V
AC/415 V AC
(tolerance ± 1%,
line voltage)
3 Routine Maintenance
Troubleshooting
For details, see the
smart cooling
product documents.
For details, see the
power supply and
power distribution
device documents.
Check the
communication
status and cables are
securely connected.
Troubleshooting
If the input voltage
is abnormal, check
the power grid
status and input
cable connection.
If the output
voltage is
abnormal, check
the UPS running
status and check
whether an alarm is
20