Procedure
Step 1 Label each cable based on the corresponding ports on the access actuator.
Step 2 Disconnect cables from the access actuator.
Step 3 Remove the failure access actuator from guide rails.
Figure 6-19 Removing the access actuator
Step 4 Install the reserved access actuator in the original position and connect the cables.
Step 5 Synchronize the parameters of the access actuator on the ECC800-Pro WebUI.
Step 6 Log in to the ECC800-Pro WebUI and choose System Settings > Access Management. Set
the access permission for the new access actuator according to the access permission setting
for the old access actuator. Then perform Synchronize Permission.
Step 7 On the ECC800-Pro WebUI, choose Monitoring > System > ECC800 > Controls > Delete
device with communication failure, and click Submit.
Step 8 Log in to the ECC800-Pro WebUI, and edit the plan view by adding new devices.
Step 9 Verify that the aisle access control system is normal.
----End

6.4.3.2 Replacing an Access Control Device

The replacement methods are the same for the fingerprint and card reader with a keypad,
fingerprint and card reader, and card reader with a keypad.
Impact on the System
The access control system cannot be used.
Issue 05 (2020-03-25)
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, step ladder, labels, marker