ABB ACSM1 Firmware Manual page 89

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

13.12 AI SUPERVISION
Selects how the drive reacts when analogue input signal limit is reached. The limit is selected by
parameter
13.13 AI SUPERVIS
(0) NO
(1) FAULT
(2) SPD REF SAFE
(3) LAST SPEED
13.13 AI SUPERVIS ACT
Selects the analogue input signal supervision limit.
Bit
0
AI1<min
1
AI1>max
2
AI2<min
3
AI2>min
Example: If parameter value is set to 0010 (bin), bit 1 AI1>max is selected.
0b0000...0b1111
FW block: None
ACT.
No action taken.
The drive trips on fault AI SUPERVISION.
The drive generates alarm AI SUPERVISION and sets the speed to
the speed defined by parameter
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
The drive generates alarm AI SUPERVISION and freezes the speed
to the level the drive was operating at. The speed is determined by the
average speed over the previous 10 seconds.
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
FW block: None
Supervision selected by parameter
AI1 signal value falls below the value defined by equation:
par.
13.03 AI1 MIN
- 0.5 mA or V
AI1 signal value exceeds the value defined by equation:
par.
13.02 AI1 MAX
+ 0.5 mA or V
AI2 signal value falls below the value defined by equation:
par.
13.08 AI2 MIN
- 0.5 mA or V
AI2 signal value exceeds the value defined by equation:
par.
13.07 AI2 MAX
+ 0.5 mA or V
AI1/AI2 signal supervision selection.
46.02 SPEED REF
SAFE.
13.12
AI SUPERVISION is activated if
Parameters and firmware blocks
89