Fio_11_Ai_Slot2 - ABB ACSM1 Firmware Manual

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

264

FIO_11_AI_slot2

(10089)
Illustration
Execution time
Operation
Standard function blocks
FIO_11_AI_slot2
TLA1 1 msec
AI1 filt gain
AI1 Min
AI1 Max
AI1 Min scale
AI1 Max scale
AI2 filt gain
AI2 Min
AI2 Max
AI2 Min scale
AI2 Max scale
AI3 filt gain
AI3 Min
AI3 Max
AI3 Min scale
AI3 Max scale
11.1 µs
The block controls the three analogue inputs (AI1...AI3) of a FIO-11 Analog I/O
Extension mounted on slot 2 of the drive control unit.
The block outputs both the unscaled (AIx) and scaled (AIx scaled) actual values of each
analogue input. The scaling is based on the relationship between the ranges
AIx min ... AIx max and AIx min scale ... AIx max scale.
AIx Min must be smaller than AIx Max; AIx Max Scale can be greater or smaller than AIx
Min Scale.
AIx Min Scale < AIx Max Scale
52
(1)
AI1 mode(52)
AI1 mode
AI1(52)
AI1
AI1 scaled(52)
AI1 scaled
AI2 mode(52)
AI2 mode
AI2(52)
AI2
AI2 scaled(52)
AI2 scaled
AI3 mode(52)
AI3 mode
AI3(52)
AI3
AI3 scaled(52)
AI3 scaled
Error(52)
Error
AIx scaled
32768
AIx Max Scale
-11 V or
-22 mA
AIx Min Scale
-32768
AIx [V or mA]
11 V or
22 mA