Group 45 Mot Therm Prot - ABB ACSM1 Firmware Manual

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

138
Group
45 MOT THERM PROT
Settings for thermal protection of the motor. See also section
protection
45
45 MOT THERM PROT
Firmware block:
MOT THERM PROT
(45)
Configures motor overtemperature
protection and temperature
measurement. Also shows the
estimated and measured motor
temperatures.
Block outputs located in other
parameter groups
45.01 MOT TEMP PROT
Selects how the drive reacts when motor overtemperature is detected.
(0) NO
(1) ALARM
(2) FAULT
45.02 MOT TEMP SOURCE
Selects the motor temperature protection. When overtemperature is detected the drive reacts as
defined by parameter
Parameters and firmware blocks
on page 38.
[ No ]
[ ESTIMATED ]
[ 90 C ]
[ 110 C ]
[ 20 C ]
[ 100 % ]
[ 100 % ]
[ 45.00 Hz ]
[ 80 C ]
[ 256 s ]
1.17 MOTOR TEMP
1.18 MOTOR TEMP EST
FW block:
Inactive.
The drive generates alarm MOTOR TEMPERATURE when the
temperature exceeds the alarm level defined by parameter
MOT TEMP ALM LIM.
The drive generates alarm MOTOR TEMPERATURE or trips on fault
MOTOR OVERTEMP when the temperature exceeds the alarm/fault
level defined by parameter
TEMP FLT
FW block:
45.01 MOT TEMP
MOT THERM PROT
TLF11 10 msec
1.17 MOTOR TEMP
1.18 MOTOR TEMP EST
45.01 MOT TEMP PROT
45.02 MOT TEMP SOURCE
45.03 MOT TEMP ALM LIM
45.04 MOT TEMP FLT LIM
45.05 AMBIENT TEMP
45.06 MOT LOAD CURVE
45.07 ZERO SPEED LOAD
45.08 BREAK POINT
45.09 MOTNOMTEMPRISE
45.10 MOT THERM TIME
(page 56)
(page 56)
MOT THERM PROT
(see above)
45.03 MOT TEMP ALM LIM
LIM.
MOT THERM PROT
(see above)
PROT.
Thermal motor
32
(5)
45.03
/
45.04 MOT

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents