10.11 EM STOP OFF1
Selects the source for the emergency stop OFF1. 0 = OFF1 active: The drive is stopped with the
active deceleration time.
Emergency stop can also be activated through fieldbus
See section
Emergency stop
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.12 START INHIBIT
Enables the start inhibit function. The start inhibit function prevents drive restart (i.e. protects against
unexpected start) if
• drive trips on a fault and fault is reset.
• run enable signal activates while the start command is active. See parameter
• control changes from local to remote.
• external control switches from EXT1 to EXT2 or from EXT2 to EXT1.
An active start inhibit can be reset with a stop command.
Note that in certain applications it is necessary to allow the drive to restart.
(0) DISABLED
(1) ENABLED
10.13 FB CW USED
Selects the source for the control word when fieldbus (FBA) is selected as the external start and stop
control location (see parameters
default, the source is parameter
Note: This parameter cannot be changed while the drive is running.
Value pointer: Group and index
10.14 JOG2 START
If enabled by parameter
2. 1 = Active. (Jogging function 2 can also be activated through fieldbus regardless of parameter
10.15.)
Note: This parameter cannot be changed while the drive is running.
Bit pointer: Group, index and bit
10.15 JOG ENABLE
Selects the source for enabling parameters
Note: Jogging can be enabled using this parameter only when no start command from an external
control location is active. On the other hand, if jogging is already enabled, the drive cannot be started
from an external control location apart from jog commands through fieldbus.
Bit pointer: Group, index and bit
10.16 D2D CW USED
Selects the source for the control word for drive-to-drive communication. By default, the source is
parameter
2.17 D2D MAIN
FW block:
DRIVE LOGIC
on page 50.
FW block:
DRIVE LOGIC
Start inhibit function disabled.
Start inhibit function enabled.
FW block:
DRIVE LOGIC
10.01 EXT1 START FUNC
2.12 FBA MAIN
CW.
FW block:
DRIVE LOGIC
10.15 JOG
ENABLE, selects the source for the activation of jogging function
FW block:
DRIVE LOGIC
10.07 JOG1 START
FW block:
DRIVE LOGIC
CW.
(see above)
(2.12 FBA MAIN
CW).
(see above)
10.09 RUN
(see above)
and
10.04 EXT2 START
(see above)
(see above)
and
10.14 JOG2
(see above)
Parameters and firmware blocks
77
ENABLE.
FUNC). By
START.