7
MES INTERFACE FUNCTION CONFIGURATION TOOL

7.9.1 Setting items in Server Service setting

Up to 32 items can be set in [Server service settings] within one project.
7
- 54
7.9 Server Service Setting
7.9.1 Setting items in Server Service setting
Table 7.42 Setting items in [Server service settings]
Item
Sever service name
Server type
IP address
Port No.
User name
Password/Confirm
password
Data source name
Database type
Access error notification
setting
Connection timeout
Figure 7.41 [Server service settings]
Enter a server service name. (Up to 16 characters)
Select the server type of the server computer to be accessed.
Enter a decimal IP address of the server computer where DB Connection
Service is installed.
Set a port number of the server computer.
(Range: 1024 to 65535, Default: 5112)
Set a user name used to access the server computer.
(Up to 30 characters)
Set a password used to access the server computer.
(Up to 30 characters)
Set the name of the ODBC data source to be accessed.
(Up to 30 characters)
Select the type of the database server.
Set whether to enable or disable notification of the access error status.
In case a connection error occurs on the network between the MES
interface module and the server computer, set a timeout time during which
the MES interface module will detect the error.
(Range: 1 to 180 seconds, Default: 10 seconds)