SPECIFICATIONS
CHAPTER 3 SPECIFICATIONS
This chapter explains the performance specifications, functions, buffer memory, etc. of the
MES interface module and the MX MESInterface.
For general specifications of the MES interface module, refer to the following manual.

3.1 Performance Specifications

This section explains the MES interface module and the MX MESInterface performance
specifications.
(1) Transmission and interface specifications
Item
Ethernet
CompactFlash card
Number of occupied I/O points
Clock
5VDC internal current consumption
External dimensions
Weight
3
- 1
3.1 Performance Specifications
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
Table 3.1 Transmission and interface specifications
*1
10BASE-T
Interface
Communication
Full-duplex/half-duplex
method
• Full-duplex: None (Does not support to the IEEE802.3x)
Flow control
• Half-duplex: Back pressure congestion control
Data transmission
10 Mbps
rate
Transmission method Base band
No. of cascaded
Maximum 4 stages
stages
Maximum segment
100m (length between a hub and a node)
length
The auto-negotiation function is available. (automatically distinguishes 10BASE-T from
Supported function
100BASE-TX)
Supply power voltage 3.3V ± 5 %
Supply power
Maximum 150 mA
capacity
Card size
TYPE I card
No. of installable
1
cards
32 points/slot (I/O assignment: Intelli. 32 points)
The clock data is obtained from a programmable controller CPU (in multiple CPU
system, CPU No.1) or the SNTP server computer.
• QJ71MES96N: 0.50A
• QJ71MES96: 0.69A
98 (3.86) (H) × 27.4 (1.08) (W) × 90 (3.54) (D) [mm (inch)]
• QJ71MES96N: 0.15 kg
• QJ71MES96: 0.16 kg
*1
The MES interface module distinguishes 10BASE-T from 100BASE-TX depending on the device
on other end.
For connection with a hub not having the auto-negotiation function, set the hub side to half-duplex
auto communication mode.
*2
This number applies when a repeater hub is used.
When using a switching hub, check the number of cascaded stages with the manufacturer of the
hub to be used.
*3
For the maximum segment length (a length between hubs), consult with the manufacturer of the
switching hub used.
*2
Section 6.3 Time Synchronization Function
Specifications
100BASE-TX
100 Mbps
*2
Maximum 2 stages
*3