Mitsubishi Electric Melsec Q Series User Manual page 222

Programmable contoller mes interface module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

7
MES INTERFACE FUNCTION CONFIGURATION TOOL
(2) Trigger 1, Trigger 2
Disable
Time specification startup
Specified time period
startup
Value monitoring startup
At module startup
Handshake operation
(3) Disable
7
- 64
7.10 Job Setting
7.10.2 Setting items in Trigger conditions
Select items for [Trigger 1] and [Trigger 2], referring to (3) and subsequent
descriptions.
Table 7.49 Selection items for [Trigger 1] and [Trigger 2]
Item
No trigger conditions
When the specified date, time and day of the week match
the actual date, time and day of the week, the condition
changes from false to true, resulting in job startup.
The condition is alternated between true and false in the
specified cycles (unit: seconds), and when it changes from
false to true, the job is activated.
The actual tag component value is compared with the
condition value (tag component value or constant value) at
every sampling times, and the job is activated when the
condition changes from false to true.
The job is activated only once when the MES interface
module is started up.
The job is activated when [Handshake startup] of the
programmable controller CPU turns ON.
Upon completion of the job execution, [Completion
notification] of the programmable controller CPU turns ON.
When using 'Value monitoring startup' or 'Handshake operation' for a trigger
condition, check that 'Information linkage status (X5)' is in execution (ON), and
create a program so that the trigger condition is satisfied.
Section 2.6.5 (1) Startup time
(a) When [Disable] is selected for [Trigger 1] or [Trigger 2]
Another trigger is regarded as a trigger condition.
(b) When [Disable] is selected for both [Trigger 1] and [Trigger 2]
The job is not activated by trigger conditions.
When [Disable] is selected, the job can be activated by an "instruction of job
execution" of the XML processing function.
Section 6.2 XML Processing Function
Description
(3) Disable in this section
(4) Time specification startup in this section
(5) Specified time period startup in this section
(6) Value monitoring startup in this section
(7) At module startup in this section
(8) Handshake operation in this section
Trigger 1 Trigger 2
: Selectable,
: Not selectable
×
×

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qj71mes96Qj71mes96nSw1dnc-mesif-e

Table of Contents