3
SPECIFICATIONS

3.6.10 Information linkage function area

(1) "Time synchronization" setting status (Buffer memory address: 11500)
(2) SNTP time query result (Buffer memory address: 11501 to 11507)
(3) Monitoring interval timeout count (Buffer memory address: 11510)
3
- 37
3.6 Buffer Memory Details
3.6.10 Information linkage function area
(a) The setting status of [Time synchronization setting] is stored.
For [Time synchronization setting], refer to the following.
Section 7.6.2 Setting items in Time synchronization setting
0: [Synchronize with PLC CPU time]
1: [Synchronize with SNTP]
(b) When selecting [Synchronize with SNTP] in [Time synchronization setting]
This area is set when the time information was obtained from the SNTP server
computer.
If the time information could not be obtained from the SNTP server computer, this
area is not set since the operation for when [Synchronize with PLC CPU time] is
selected is performed (Time is synchronized with the programmable controller
CPU).
When [Synchronize with SNTP] is selected in [Time synchronization setting], the time
information obtained from the SNTP server is stored.
(When [Daylight saving setting] is enabled, time corrected to daylight saving time is
stored during the period of summer time.)
Address
Name
(Decimal)
11501
SNTP time query result (Year)
SNTP time query result
11502
(Month)
11503
SNTP time query result (Day)
11504
SNTP time query result (Hour)
SNTP time query result
11505
(Minute)
SNTP time query result
11506
(Second)
SNTP time query result (Day of
11507
the week)
The cumulative number of times that a monitoring interval timeout has occurred is
stored.
The monitoring interval timeout occurs when trigger detection has not been completed
within the monitoring interval.
If this timeout occurs, perform the following:
• Increase the monitoring interval
Increase the sampling interval of the tag that is used for trigger conditions.
• Reduce the trigger detection time.
Reduce the number of configured jobs.
Table 3.19 SNTP time query result
The four-digit year data is stored.
The month data, 01 to 12, is stored.
The day data, 01 to 31, is stored.
The hour data, 00 to 23, is stored.
The minute data, 00 to 59, is stored.
The second data, 00 to 59, is stored.
The day of the week data is stored.
0: Sunday 1: Monday 2: Tuesday
3: Wednesday 4: Thursday 5: Friday
6: Saturday
Description
Set on system
Setting side
side