10
TROUBLESHOOTING
Error code
*1
0x20400020
0x20400021
*1
0x20400022
0x20400023
0x20500011
0x20500012
0x20500020
to
0x20500022
0x20600001
*1
0x20600002
0x20600010
0x20600011
0x20600012
0x20600020
Table 10.7 Access log output error list of DB Connection Service
Error description and cause
(SID [Session ID]: DB Connect: [Data source]:
[User]: Failed)
Failed to create a DB handle.
System error
(SID [Session ID]: DB Connect: [Data source]:
[User]: Failed)
Failed in DB connection.
System error
(SID [Session ID]: SQL<...>: Failed)
(SID [Session ID]: COMMIT: Failed)
(SID [Session ID]: ROLLBACK: Failed)
(SID [Session ID]: GetNext: Failed)
(SID [Session ID]: Reset: Failed)
Failed in SQL execution due to insufficient memory.
(SID [Session ID]: SQL<...>: Failed)
(SID [Session ID]: COMMIT: Failed)
(SID [Session ID]: ROLLBACK: Failed)
(SID [Session ID]: GetNext: Failed)
(SID [Session ID]: Reset: Failed)
Failed in SQL execution due to insufficient
resources.
(SID [Session ID]: SQL<...>: Failed)
(SID [Session ID]: COMMIT: Failed)
(SID [Session ID]: ROLLBACK: Failed)
(SID [Session ID]: GetNext: Failed)
(SID [Session ID]: Reset: Failed)
Invalid SQL execution request
System error
(SID [Session ID]: SQL<...>: Failed)
(SID [Session ID]: COMMIT: Failed)
(SID [Session ID]: ROLLBACK: Failed)
(SID [Session ID]: GetNext: Failed)
(SID [Session ID]: Reset: Failed)
DB Connection Service does not support the SQL
instruction to be executed.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Please consult your local Mitsubishi
representative.
• Set correct data source name, user name, and
password in [Server service settings] of MES
Interface Function Configuration Tool.
• To use a 64-bit version operating system for the
server, type the following at the command
prompt to start the "ODBC Data Source
Administrator".
%SystemRoot%\SysWOW64\odbcad32.exe
• Please consult your local Mitsubishi
representative.
• Terminate any unnecessary applications.
• Add more memory to the personal computer.
• Check if the source IP address belongs to the
MES interface module or the configuration
computer.
• Check the version of the MES interface module
or MES Interface Function Configuration Tool.
• Please consult your local Mitsubishi
representative.
• Check if the source IP address belongs to the
MES interface module or the configuration
computer.
• Check the version of the MES interface module
or MES Interface Function Configuration Tool.
10.2 Error Code List
10.2.2 Error codes of DB Connection Service
(From the previous page)
Corrective action
(To the next page)
10
- 30
9
10