8
DB CONNECTION SERVICE AND SETTING TOOL
(1) Service port (required) (Range: 1024 to 65535, Default: 5112)
(2) DB access timeout (required) (Range: 1 to 3600, Default: 30)
8
- 16
8.5 Setting Items of DB Connection Service Setting Tool
Figure 8.8 DB Connection Service Setting Tool
Table 8.3 Setting items of DB Connection Service Setting Tool
Item
Service port (required)
Set the port number where the DB Connection Service operates.
Set a DB access timeout (Unit: seconds) for the case where no response is
DB access timeout
returned to the MES interface module after requesting the server computer
(required)
for value writing to or reading from the database or for a program execution.
Limit IP addresses permit
Specify whether or not to set the IP addresses permitted to connect.
to connect
Output access log
Set whether or not to output the access log.
Output SQL failed log
Set whether or not to output the SQL failure log.
Specify the character code of the log file (access log, SQL failure log) that is
Log character code
output by DB connection service in ASCII/SJIS or Unicode.
Set the port number where the DB Connection Service operates.
The set port number is used for communications with the MES interface module or the
configuration computer.
*1
Set the same value in [Service port] as the one set in [Server service settings] - [Port No.] of MES
Interface Function Configuration Tool.
Section 7.9.1 Setting items in Server Service setting
*2
Specify the number of the port that is not being used by any database or another application.
Usually, it need not be changed.
Set a DB access timeout (Unit: seconds) for the case where no response is returned
to the MES interface module or the configuration computer after requesting the server
computer for value writing to or reading from the database or for a program execution.
When a timeout occurs, the connection with the MES interface module or the
configuration computer is disconnected and job execution is canceled.
Set a value to [DB access timeout] so that the relation with a value set in
[Connection timeout] in [MES Interface Configuration Tool] is as follows:
• Connection timeout value
Description
DB access timeout value
*1 *2