Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 92

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Processing details
■Engineering value conversion processing
This function block executes range conversion to the value input from the input variable IN and outputs the result from the
output variable OUT_.
Output (OUT_)
OUT_NMAX
OUT_NMIN
IN_NMIN
(OUT_NMAX-OUT_NMIN)×(IN-IN_NMIN)
OUT_=
IN_NMAX-IN_NMIN
OUT_NMAX: Output High Limit Alarm
OUT_NMIN: Output Low Limit Alarm
IN: Input value (IN_NMIN to IN_NMAX)
OUT_: Output value
This expression is also applicable for OUT_NMAX  OUT_NMIN and N_NMAX  N_NMIN.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (IN) or operation constant (IN_NMAX, IN_NMIN, OUT_NMAX, OUT_NMIN) is a subnormal number or NaN (not a number).
3403H
An overflow has occurred.
5 CORRECTION OPERATION
90
5.9 Range Conversion (M+P_RANGE_)
Input (IN)
IN_NMAX
+ OUT_NMIN