10.23
3 position ON/OFF Control (Disable Tracking for
primary loop) (M+P_ONF3)
M+P_ONF3
This FB performs three-position (on/off) control.
FBD/LD
M+P_ONF3
PVP
MVP
CASIN
CASOUT
MVB1
MVB2
Applicable tag type
ONF3
Control mode
MAN
AUT
■Block diagram
PVP
(%)
Engineering
CASIN
(%)
value
conversion
CAS
Tag data
Setting data
■Input/output variable
Variable
Description
name
PVP
PV input (unit: %)
CASIN
Cascade SV input (unit: %)
MVP
MV output (unit: %)
CASOUT
Cascade output (unit: %)
ON/OFF output (turns on at MV  75%)
MVB1
MVB2
ON/OFF output (turns on at MV < 25%)
CAS
M+P_ONF3
-
Inverse
engineering
value
conversion
SV
SV

10.23 3 position ON/OFF Control (Disable Tracking for primary loop) (M+P_ONF3)

CMV
MV
correction
AUT,
CAS,
MAN,
CSV
CMV
MV
MV
Recommended
Type
range
0 to 100[%]
Input variable
0 to 100[%]
Input variable
0 to 100[%]
Output variable
0 to 100[%]
Output variable
TRUE: On
Output variable
FALSE: Off
TRUE: On
Output variable
FALSE: Off
10 LOOP CONTROL OPERATION
CSV
(%)
MVP
(%)
CASOUT
MVB1
3 position
(Bit output)
ON/OFF
MVB2
control
(Bit output)
Data type
REAL
REAL
REAL
REAL
BOOL
BOOL
10
305