Mitsubishi Electric MELSEC iQ-R Series Programming Manual page 607

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Cascade connection when tracking is not required
Connect CASOUT of the primary loop with CASIN of the secondary loop. The tag FB of the secondary loop should be the one
with CASIN.
(1)
1
(1) Primary loop
(2) Secondary loop
When tracking is not executed, the operation constant of the secondary loop tag FB is as follows.
Variable name
Description
PID_SVPTN_BO
Setting value (SV) used
(2)
2
Range
Initial value
TRUE: Not used
TRUE
FALSE: Used
Setting for tracking
FALSE
Appendix 3 Related Functions of Process
A
APPX
605