■Disable alarm detection
This function block sets whether to detect alarms (ALM) or not.
Item
Disable alarm detection by setting tag data
Operation error
There is no operation error.
If another command is issued while a command pulse signal (TRUE) is output from the output variable FWD,
STOP_, or REV, the command pulse signals (TRUE) are output simultaneously.
<When multiple command pulse signals (TRUE) are output>
FWD command input signal from faceplate or
input FWD_SET (Detected at rising edge)
Command pulse signal from output pin FWD
(output variable FWD)
STOP command input signal from faceplate or
input STOP_SET (Detected at rising edge)
Command pulse signal from output pin STOP_
(output variable STOP_)
When the output variables FWD, STOP_, and REV are output directly to the external device, multiple
commands (FWD command, STOP command, and REV command) may be output simultaneously to the
external device.
Not to output multiple commands to the external device simultaneously, create a program to output only either
one of the command pulse signals to the external device.
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, no TRIPA
and TOA of the alarm (ALM) will be detected.
• ERRI
• TRIPI
• TOI
Command pulse period (DOT)
Command pulse period (DOT)
: Time when command pulse signals are output
simultaneously (TRUE)
13.2 Motor Reversible (2 Input/3 Output) (M+M_REV)
t
t
t
t