3 position ON/OFF Control (Disable Tracking for
primary loop) (M+M_ONF3)
M+M_ONF3
This FB performs three-position (on/off) control combining the functions of M+P_IN, M+P_PHPL, and M+P_ONF3 into a
single FB.
FBD/LD
M+M_ONF3
PVN
MVP
CASIN
CASOUT
MVB1
MVB2
Applicable tag type
ONF3
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
PVN
IN function
(M+P_IN)*
CASIN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
PVN
Input from a module
CASIN
Primary loop SV input (Unit: %)
MV output (Unit: %)
MVP
CASOUT
Cascade MV output (Unit: %)
ON/OFF output (turns on at MV  75%)
MVB1
MVB2
ON/OFF output (turns on at MV < 25%)
12 LOOP TAG
406

12.26 3 position ON/OFF Control (Disable Tracking for primary loop) (M+M_ONF3)

AUT
CAS
PHPL function
(M+P_PHPL)*
CMV
M+M_ONF3
ONF3 function
(M+P_ONF3)*
Recommended range
-999999 to 999999
0 to 100[%]
0 to 100[%]
0 to 100[%]
TRUE: ON
FALSE: OFF
TRUE: ON
FALSE: OFF
CSV
MV(%)
MVP
CASOUT
MV(%)
MVB1
(Bit output)
MVB2
(Bit output)
Type
Data type
Input variable
REAL
Input variable
REAL
Output variable
REAL
Output variable
REAL
Output variable
BOOL
Output variable
BOOL