10.24
Program Setter (M+P_PGS)
M+P_PGS
This FB registers time width sets and setting value programs of up to 16 steps, and outputs a setting value corresponding to
the progress time of each step with linear interpolation. ( Page 615 Program setter (PGS))
FBD/LD
M+P_PGS
MVP
CASOUT
Applicable tag type
PGS
Control mode
MAN
■Block diagram
Pattern operation (PGS operation)
MVpgs
(MV2,SV2)
(MV1,SV1)
MAN,
CMV
Tag data
* Indicates bit item.
Setting data
■Input/output variable
Variable
Description
name
MVP
MV output (unit: %)
CASOUT
Cascade output (unit: %)
■Tag data
For details on tag data that is read or written with this tag access FB, refer to the following.
Page 547 PGS
10 LOOP CONTROL OPERATION
308
10.24 Program Setter (M+P_PGS)
AUT
(MVpgs)
(MVi-1,SVi-1)
(MVn,SVn)
(MVi,SVi)
SV
Disable alarm
CAS,
AUT,
MAN,
detection
AUT,
CAS,
CMV
CSV
CSV
SV
SV
CAS
M+P_PGS
High/low
limit limiter
AUT,
CAS,
MAN,
CSV
CMV
MHA
MLA
(*)
Alarm
CMV
(%)
(%)
MV
MV
Recommended
Type
range
0 to 100[%]
Output
variable
0 to 100[%]
Output
variable
CSV
MVP
CASOUT
Data type
REAL
REAL