Monitor (M+M_Moni) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.27

Monitor (M+M_MONI)

M+M_MONI
This FB performs monitoring combining the functions of M+P_IN and M+P_PHPL into a single FB.
FBD/LD
M+M_MONI
PVN
PVP
Applicable tag type
MONI
Control mode
MAN
■Block diagram
PVN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
PVN
Input from a module
PVP
PV output (Unit: %)
■Public variable (operation constant)
Variable
Description
name
IN_NMAX
Input High Limit
IN_NMIN
Input Low Limit
IN_HH
High Limit Range Error
IN_H
High Limit Range Error Reset
IN_L
Low Limit Range Error Reset
IN_LL
Low Limit Range Error
■Tag data
For details on tag data that is read or written with this tag FB, refer to the following.
Page 533 MONI
12 LOOP TAG
408
12.27 Monitor (M+M_MONI)
AUT
IN function
PHPL function
(M+P_IN)*
(M+P_PHPL)*
CAS
CMV
M+M_MONI
Recommended range
-999999 to 999999
0 to 100[%]
Recommended range
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
-999999 to 999999
CSV
(%)
PVP
Type
Data type
Input variable
REAL
Output variable
REAL
Initial value
Set by
100.0
User
0.0
User
102.0
User
100.0
User
0.0
User
-2.0
User
Data type
REAL
REAL
REAL
REAL
REAL
REAL

Advertisement

Table of Contents
loading

Table of Contents