I-PD Control (Disable Tracking for primary loop)
(M+M_IPD)
M+M_IPD
This FB performs I-PD control combining the functions of M+P_IN, M+P_PHPL, M+P_IPD, and M+P_OUT1 into a single FB.
FBD/LD
M+M_IPD
PVN
MVN
CASIN
CASOUT
CASOUT_T
Applicable tag type
IPD
Control mode
MAN
■Block diagram
MCHG function
(M+P_MCHG)*
PVN
IN function
(M+P_IN)*
CASIN
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable
Description
name
PVN
Input from a module
CASIN
Primary loop SV input (Unit: %)
MVN
Output to a module
CASOUT
Cascade MV output (Unit: %)
CASOUT_T
Cascade MV output (Unit: %) (With tracking) (Indirect
address)
12 LOOP TAG
388

12.18 I-PD Control (Disable Tracking for primary loop) (M+M_IPD)

AUT
CAS
PHPL function
(M+P_PHPL)*
CMV
M+M_IPD
IPD function
OUT1 function
(M+P_IPD)*
(M+P_OUT1)*
Recommended range
-999999 to 999999
0 to 100[%]
OUT1_NMIN to
OUT1_NMAX
0 to 100[%]
0 to 100[%]
CSV
MVN
MV(%)
CASOUT
MV(%)
CASOUT_T
(Tracking)
Type
Data type
Input variable
REAL
Input variable
REAL
Output variable
REAL
Output variable
REAL
Output variable
DWORD