2-Degree-Of-Freedom Pid Control (Enable Tracking For Primary Loop) (M+M_2Pid_T) - Mitsubishi Electric MELSEC iQ-R Series Programming Manual

Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

12.5
2-degree-of-freedom PID Control (Enable Tracking
for primary loop) (M+M_2PID_T)
M+M_2PID_T
This FB performs two-degree-of-freedom PID control combining the functions of M+P_IN, M+P_PHPL, M+P_2PID_T, and
M+P_OUT1 into a single FB. The primary loop can be tracked.
FBD/LD
M+M_2PID_T
PVN
MVN
CASIN_T
CASOUT
CASOUT_T
Applicable tag type
2PID
Control mode
MAN
AUT
■Block diagram
MCHG function
(M+P_MCHG)*
PVN
IN function
(M+P_IN)*
CASIN_T
(Tracking)
* (M+P_ ) indicates the main structure member tag access FB which is the main component of each function.
Setting data
■Input/output variable
Variable name
Description
PVN
Input from a module
CASIN_T
Primary loop SV input (Unit: %) (With tracking)
(Indirect address)
MVN
Output to a module
CASOUT
Cascade MV output (Unit: %)
CASOUT_T
Cascade MV output (Unit: %) (With tracking)
(Indirect address)
CAS
M+M_2PID_T
2PID function
PHPL function
(M+P_2PID_T)*
(M+P_PHPL)*
(With auto tuning function)
Recommended range
-999999 to 999999
0 to 100[%]
OUT1_NMIN to
OUT1_NMAX
0 to 100[%]
0 to 100[%]

12.5 2-degree-of-freedom PID Control (Enable Tracking for primary loop) (M+M_2PID_T)

CMV
CSV
OUT1 function
(M+P_OUT1)*
MV(%)
MV(%)
(Tracking)
Type
Input variable
Input variable
Output variable
Output variable
Output variable
12
MVN
CASOUT
CASOUT_T
Data type
REAL
DWORD
REAL
REAL
DWORD
12 LOOP TAG
351