■Processing operation
: Performed, : Not performed
Control mode
MAN, CMV, AUT, CAS, CSV,
CASDR
*1 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
Operation error
Error code
Description
(SD0)
3400H
An invalid operation (such as division by zero) is performed.
3402H
Input data (PVN), block memory, operation constant (NMAX, NMIN, HH, H_, L_, LL) or tag data is a subnormal number or NaN (not a
number).
3403H
An overflow has occurred.
3405H
High limit range error occurrence (HH) < high limit range error return (H_), low limit range error return (L_) < low limit range error
occurrence (LL), or input high limit (NMAX) < input low limit (NMIN)
Initial values of the high/low range error and high/low range error reset are based on the default input range of
the analog input module. The values are digital values converted into values in percentage. To change the
input range, change the initial values as necessary.
9 I/O CONTROL
148
9.1 Analog Input Processing (M+P_IN)
Processing operation
Range check
Input limiter
Engineering
Digital filter
value inverse
conversion
Alarm
*1