Process control function blocks
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

■Output conversion
This function block performs output conversion processing.
Converted output (MVN)
NMAX
NMIN
(-10(%))
0(%)
Converted output (MVN)
={(NMAX-NMIN)×
NMAX: Output conversion high limit value
NMIN: Output conversion low limit
MV: Manipulated value (%)
MVN: Output conversion output value
■Disable alarm detection
This function sets whether to detect alarms (ALM) or not in the deviation check and variation rate & high/low limiter
processing.
Item
Disable alarm detection by setting tag data
Disable alarm detection by control mode selection
Disable alarm detection by loop stop processing
■Loop stop processing
When the stop alarm (SPA) of the alarm (ALM) is TRUE, this function block performs the following processing.
• Outputs (MVN) are held.
• The control mode is automatically switched to MANUAL.
• When DVLA, DMLA, MHA, or MLA of the alarm (ALM) has occurred, the DVLA, DMLA, MHA, or MLA is reset.
• No alarm is detected in the variation rate & high/low limiter processing.
■Processing operation
: Performed, : Not performed
Control
Processing operation
mode
Deviation
check
MAN, CMV
AUT
CAS, CSV
*1 Tracking is performed when the tracking flag (TRK) is 1.
*2 An alarm (ALM) whose corresponding bit is TRUE (detected) is reset, and the alarm will not be detected.
*3 An alarm whose corresponding bit is TRUE (Valid) in the disable alarm detection (INH) is not detected.
10.11 Position Type PID Control (Enable Tracking for primary loop/Enable Tracking from secondary loop) (M+P_PIDP_EX_T_)
100(%)
(110(%))
MV
}+NMIN
100
PIDP
Engineering
Inverse
operation
value
engineering
conversion
value
conversion
Manipulated variable (MV)
Disable alarm detection processing
If the following bits in the disable alarm detection (INH) are TRUE, DVLA,
DMLA, MHA, or MLA of the alarm (ALM) will not be detected.
• ERRI
• DVLI
• DMLI
• MHI
• MLI
In the MAN or CMV mode, DVLA, DMLA, MHA, and MLA of the alarm (ALM)
are reset and the DVLA, DMLA, MHA, or MLA will not be detected.
Page 249 Loop stop processing
Variation
Output
rate & high/
conversion
low limiter
10 LOOP CONTROL OPERATION
Tracking
Alarm
*1
*2
*1
*3
*3
249
10